Color Coding (Cable Wiring)
The conductors in nonmetallic-sheathed cable (Romex) are color coded with insulation as follows:
2-wire: one black (“hot” phase conductor)one white (grounded “identified” conductor)one bare, covered, or insulated (equipment grounding conductor)
3-wire: one black (“hot” phase conductor) one white (grounded “identified” conductor) one red (“hot” phase conductor) one bare, covered, or insulated (equipment grounding conductor)
4-wire: one black (“hot” phase conductor) one white (grounded “identified” conductor) one red (“hot” phase conductor) one blue (“hot” phase conductor) one bare, covered, or insulated (equipment grounding conductor)
Four-wire nonmetallic-sheathed cable is also available with two ungrounded (“hot”) and two neutral conductors. This cable is designed for wiring two 120-volt branch circuits without using a common neutral.
This avoids the requirement of installing a tie handle on the circuit breakers or installing a 2-pole circuit breaker. This cable has the following insulated conductors:
• one black (“hot” phase conductor)
• one white with a black stripe (grounded “identified” conductor)
• one red (“hot” phase conductor)
• one white with a red stripe (“hot” phase conductor)
• one bare, covered, or insulated (equipment grounding conductor)
Manufacturers of Type MC cable also make a “home run cable.” This cable is available with 6 or 8 12 AWG conductors and with 6, 8, 12, and 16 10 AWG conductors. The insulation is THHN/THWN, so
derating [required by NEC 310.15(B)(3)] is started in the 90°C column of NEC Table 310.15(B) (16).
Table 5-1 illustrates application of derating for the number of current-carrying conductors in the home run cable. Notice that the number of currentcarrying conductors can change depending on how connections are made.
Transmission Lines Design, Electrical Engineering Calculations, Substation Notes, Line Parameters, Relay Protection Tutorials, and Engineering Guides for Students and Professionals.
Subscribe to:
Post Comments (Atom)
Ferranti Effect vs. Corona Effect vs. Reactive Power Effects
Ferranti Effect vs. Corona Effect vs. Reactive Power Effects A complete technical comparison for long AC transmission lines This is a n...
-
When a conductor is covered with ice and/or is exposed to wind, the effective conductor weight per unit length increases. During occasions o...
-
Hello. In this blog, we will try to create a steel pole model, using the PLS Pole software of Power Lines System. This created pole will pr...
-
Yup, you read it right. This is about the World's Longest Overhead Transmission Line as of today. It is around 1700 km in length, trans...

1 comment:
Anyone have preferred residential wiring contractors they use or have heard of? One of the guys I refer to regularly.
TechFlex
Post a Comment