RESIDENTIAL WIRING COLOR CODING (CABLE WIRING) BASICS AND TUTORIALS

Color Coding (Cable Wiring)
The conductors in nonmetallic-sheathed cable (Romex) are color coded with insulation as follows:

2-wire: one black (“hot” phase conductor)one white (grounded “identified” conductor)one bare, covered, or insulated (equipment grounding conductor)

3-wire: one black (“hot” phase conductor) one white (grounded “identified” conductor) one red (“hot” phase conductor) one bare, covered, or insulated (equipment grounding conductor)

4-wire: one black (“hot” phase conductor) one white (grounded “identified” conductor) one red (“hot” phase conductor) one blue (“hot” phase conductor) one bare, covered, or insulated (equipment grounding conductor)

Four-wire nonmetallic-sheathed cable is also available with two ungrounded (“hot”) and two neutral conductors. This cable is designed for wiring two 120-volt branch circuits without using a common neutral.

This avoids the requirement of installing a tie handle on the circuit breakers or installing a 2-pole circuit breaker. This cable has the following insulated conductors:

• one black (“hot” phase conductor)
• one white with a black stripe (grounded “identified” conductor)
• one red (“hot” phase conductor)
• one white with a red stripe (“hot” phase conductor)
• one bare, covered, or insulated (equipment grounding conductor)

Manufacturers of Type MC cable also make a “home run cable.” This cable is available with 6 or 8 12 AWG conductors and with 6, 8, 12, and 16 10 AWG conductors. The insulation is THHN/THWN, so
derating [required by NEC 310.15(B)(3)] is started in the 90°C column of NEC Table 310.15(B) (16).

Table 5-1 illustrates application of derating for the number of current-carrying conductors in the home run cable. Notice that the number of currentcarrying conductors can change depending on how connections are made.



Comments

Luke20 said…
Anyone have preferred residential wiring contractors they use or have heard of? One of the guys I refer to regularly.

TechFlex

Popular posts from this blog

POLYMERIC INSULATON OF POWER CABLES BASICS AND TUTORIALS

ENTRY LEVEL and SENIOR ENGINEERING JOBS

SURGE ARRESTER ENERGY HANDLING CAPABILITY FOR TRANSMISSION AND DISTRIBUTION LINES APPLICATION TUTORIALS

free counters