Posts

Showing posts from 2013

DIFFERENTIAL CALCULUS PLATES FOR 6:30 and 7:30 CLASSES

Please submit on or before 12:00 nn of January 6, 2013. Those submitted after the said date and time will be marked zero (0). 1. At what values of x does the graph of y = sec x have a horizontal tangent? 2. Find the derivate of Csc (3x - 5). 3. Find the first derivative of y = cos x / 1 - sin x. 4. Find an equation of the tangent line at the point P = (1, 1) on the curve  y 4 + xy = x 3 − x + 2 5. Find y' if y = sin( cos x) 6. A person x inches tall has a pulse rate of y beats per minute, as given approximately by y = 590x-1/2          30 ≤ X ≤ 75 What is the instantaneous rate of change of pulse rate at the (A) 36-inch level? (B) 64-inch level? 7. Suppose that a person learns y items in x hours, as given by y = 50 √ x,  0  ≤  X  ≤ 9 Find the rate of learning at the end of (A) 1 hour (B) 9 hours GOOD LUCK. MERRY CHRISTMAS AND HAPPY NEW YEAR LEO

SYNCHRONOUS GENERATOR AS FAULT CURRENT SOURCE

If a short circuit is applied to the terminals of a synchronous generator, the short-circuit current starts out at a high value and decays to a steady-state value some time after the inception of the short circuit. Since a synchronous generator continues to be driven by its prime mover and to have its field externally excited, the steady-state value of short-circuit current will persist unless interrupted by some switching means. An equivalent circuit consisting of a constant driving voltage in series with an impedance that varies with time is used to represent this characteristic. The varying impedance consists primarily of reactance. Xd"= subtransient reactance; determines current during Þrst cycle after fault occurs. In about 0.1 s reactance increases to Xd'= transient reactance; assumed to determine current after several cycles at 60 Hz. In about 0.5 to 2 s reactance increases to Xd = synchronous reactance; this is the value that determines the current ßow after...

MEASUREMENT OF PHASE VOLTAGE UNBALANCE IN THREE PHASE SYSTEM

Causes of phase-voltage unbalance Most utilities use four-wire grounded-wye primary distribution systems so that single-phase distribution transformers can be connected phase-to-neutral to supply single-phase loads, such as residences and street lights. Variations in single-phase loading cause the currents in the three-phase conductors to be different, \ producing different voltage drops and causing the phase voltages to become unbalanced. Normally the maximum phase-voltage unbalance will occur at the end of the primary distribution system, but the actual amount will depend on how well the single-phase loads are balanced between the phases on the system. Perfect balance can never be maintained because the loads are continually changing, causing the phase-voltage unbalance to vary continually. Blown fuses on three-phase capacitor banks will also unbalance the load and cause phase-voltage unbalance. Industrial plants make extensive use of 480Y/277 V utilization voltage to supply l...

BARE COPPER CONDUCTORS AMPACITY AND TABLE

Image
Conductor current–carrying capacity, or ampacity, is determined by the maximum safe operating temperature of the insulation used on the conductor. Heat generated as a result of current flow is dissipated into the environment. Thus, for a given installation context (open-air, buried in earth, or enclosed), ampacity increases with increasing conductor size and with maximum permissible insulation temperature. If more than three conductors are placed in a conduit, the resultant increase in temperature requires that the conductors be derated to maintain safe operating conditions. Because heat dissipation from a conductor in free air is much greater than that from the same conductor enclosed in conduit or directly buried, its corresponding allowable ampacity is also greater. Conversely, if the ambient temperature around a conductor is higher than 30ºC (86ºF), the temperature upon which all standard ampacity tables are based, the permissible ampacity must be reduced. Ampacity table...

COPPER CLAD ALUMINUM WIRE/ CONDUCTORS BASIC INFORMATION

What are copper clad aluminum conductors? Copper-clad aluminum is the newest conductor material on the market. A copper-clad aluminum conductor is drawn from copper-clad aluminum rod, the copper being bonded metallurgically to an aluminum core. The copper forms a minimum of 10 percent of the cross-sectional area of the solid conductor or of that of each strand of a stranded conductor. Although copper-clad aluminum contains only 10 percent of copper by volume (26.8 percent by weight), its electrical performance is equivalent to that of pure copper. It is lighter and easier to handle, and the price advantage, which reflects the value of the copper content, can be as much as 25 percent when copper peaks to one of its periodic highs. Detailed studies by Battelle Laboratories have shown that copper-clad aluminum and copper have the same connection reliability. Because the electrical industry consumes 60 percent of all copper used in the United States, it is critically affected by copp...

METAL-ENCLOSED INTERRUPTER SWITCHGEAR PRODUCTION TESTS

Production Tests Unless otherwise specified, all production tests shall be made by the manufacturer at the factory on the complete MEI switchgear or its component for the purpose of checking the correctness of manufacturing operations and materials. (See ANSI/IEEE C37.20.3-1987.) Production tests shall include the following: 1) Low-frequency withstand voltage tests 2) Mechanical operation tests 3) Grounding of instrument transformer cases test 4) Electrical operation and wiring tests Low-Frequency Withstand Voltage Tests Low-frequency withstand tests shall be made at the factory on each switchgear assembly in the same manner as described in 4.5.2 with the exception that tests across the open gap(s) (see 4.5.1(2)) are not required. Tests shall be made in accordance with 4.5.1(1) and 4.5.2.2. Drawout interrupter switch removable elements need not be tested in the assembly if they are tested separately. Control devices, potential transformers, and control power transformers, which are...

SWITCHGEAR ASSEMBLIES FOR NUCLEAR GENERATING PLANTS SERVICE CONDITIONS

The service conditions below are significant to the qualification of switchgear assemblies and included components.   Usual Service Conditions The values given as usual service conditions represent the anticipated average conditions for switchgear assemblies in nuclear power generating stations. These values are recommended for use in generic qualification programs and do not imply a derating of the equipment.   Ambient Temperature A yearly average ambient temperature of 30 °C with temperature excursions to 10 °C and 40 °C is considered usual.   Relative Humidity Relative humidity variations between 10% and 90% are considered usual.   Altitude Altitudes of up to 6600 ft (2000 m) above sea level for metal-enclosed low-voltage power circuit breaker switchgear and up to 3300 ft (1000 m) for metal-clad switchgear and metal-enclosed interrupter switchgear are considered usual.   Radiation Radiation exposure of up to 104 rads equivalent gamma tota...

DISTRIBUTION AUTOMATION - A GUEST POST BY DARYLL VALDEZ

Today's post is brought to us by our guest. He is Daryll Valdez, a student from the University of Mindanao, in the Philippines. Darryl is currently finishing his Bachelor's Degree in Electrical Engineering.  Distribution Automation Daryll Valdez A Distribution Automation (DA) System enhances the efficiency and productivity of a utility. It also provides intangible benefits such as improved public image and market advantages. A utility should evaluate the benefits and costs of such a system before committing funds. The expenditure for distribution automation is economical when justified by the deferral of a capacity increase, a decrease in peak power demand, or a reduction in O&M requirements. Distribution Automation Systems have been defined by the Institute of Electrical and Electronic Engineers (IEEE) as systems that enable an electric utility to monitor, coordinate, and operate distribution components in a real-time mode from remote locations.  The DA Sys...

TRANSMISSION LINE MATERIALS HANDLING AND STORAGE

In the unloading, handling, and storage of structures, care should be exercised so as not to damage the surface or surface coating, or deform the members. Bare wire rope or steel chains should not be used for handling without adequate protection of the surface. Structural members should not be dumped, dragged, rolled, dropped, nor used as loading or unloading skids or blocking.   Heavy members should not be stacked on top of lighter members. The maximum weight of material bundles should not exceed a specified weight, typically 1600–1800 kg (3500–4000 lb), to facilitate handling and unloading. Components with dissimilar finishes should not be stored over one another to minimize discoloration of the lower members. Care should be taken to ensure proper blocking, stacking, and handling of concrete members. Refer to the structure drawings and instructions to verify correct lifting methods, replacement of support blocking, and stacking limitations.   It is very common for...

ELECTRIC BUS WAYS CURRENT RATING BASIC INFORMATION

Image
To apply busways properly in an electric power distribution system, some of the more important items to consider are the following. Current-carrying capacity Busways should be rated on a temperature-rise basis to provide safe operation, long life, and reliable service. Conductor size (cross-sectional area) should not be used as the sole criterion for specifying busway. Busway may have seemingly adequate cross-sectional area and yet have a dangerously high temperature rise. The UL requirement for temperature rise (55 deg C) (see ANSI/UL 857-1989) should be used to specify the maximum temperature rise permitted. Larger crosssectional areas can be used to provide lower voltage drop and temperature rise. Although the temperature rise will not vary significantly with changes in ambient temperature, it may be a significant factor in the life of the busway. The limiting factor in most busway designs is the insulation life, and there is a wide range of types of insulating materials used b...

FAULT ARC PATH OF TRANSMISSION LINE BASIC INFORMATION

When lightning strikes a transmission line the field intensity stressing the insulation may exceed the ionization field intensity level (roughly 30kV/cm) and create an arc from the line to ground. A path now exists for current flow. The resulting discharge current flow from the lightning stroke is usually over within a few milliseconds but the ionized path has been established and a 60Hz “follow” current flows. This current must be detected and interrupted by deenergizing the line with circuit breakers. For the ionization path to dissipate, the voltage must be absent for a sufficient duration. The time during which the voltage is absent is commonly called “dead” time. For transient faults to be successfully cleared, an adequate time for deionization must be afforded. Table 1 shows the minimum time required by voltage level and by probability of successfully reclosing and energizing the line. Table 1. Minimum De-Ionization Time for Reclosing Breakers System Voltage  ...

SERIES COMPENSATED TRANSMISSION LINES BASIC INFORMATION

Series compensation of long high-voltage and extra-high-voltage lines has become almost standard practice. The presence of series compensation affects the X0/X1 ratios of the system, with the reactance of the series capacitor appearing in all three sequence networks. Therefore, temporary and transient overvoltages as a result of faults, as well as circuitbreaker recovery voltages and surge arrester operation, are different than those that would appear in the uncompensated system. There have also been concerns about ferroresonant TOVs in series-compensation systems , but few if any cases of ferroresonance have been reported for operating transmission or subtransmission systems. However, because of this concern, some utilities buying series capacitors have specified special subharmonic detection devices as part of the series capacitor bank. There are also concerns about subsynchronous resonance (SSR) of rotating machine mechanical systems with the series compensated electrical system...

CONNECTION AND TERMINATIONS OF METAL CLAD SWITCHGEARS BASIC INFORMATION

Bus connections When the MC switchgear consists of several shipping sections, the main bus is necessarily disconnected before shipping. The main bus should be reconnected, with particular attention paid to the cleanliness of and pressure between the contact surfaces. It is essential that the connections be securely bolted because the conductivity of the joints is dependent on the applied pressure. Refer to the manufacturer’s torque recommendations and any other special instructions. Cable connections Before the cable connections are made, the phasing of each cable should be determined in accordance with the connection diagram, and the cables should be tagged accordingly. The cable manufacturer’s instructions should be followed in forming cable terminations and during the installation of the cable. It is essential that the connections be clean and torqued to manufacturer’s recommendations since the conductivity of the joints is proportional to the applied pressure. The terminating ...

PAD MOUNTED FUSED SWITCHGEAR RATING INFORMATION

Overall ratings The overall ratings of PMFSG shall include the following: a) Rated power frequency; b) Rated maximum voltage; c) Rated lightning-impulse withstand voltage; d) Rated power-frequency withstand voltage; e) Rated short-circuit current. Rated power frequency The rated power frequency shall be the frequency at which the PMFSG and its components are designed to operate. The preferred rated power frequency is 50 Hz or 60 Hz. Rated maximum voltage The rated maximum voltage of PMFSG shall be that of the way with the lowest rating. A three-phase PMFSG containing one or more ways with components, such as fuses, single-phase switches, or fused-loadbreak devices rated for phase-to-ground voltage (maximum voltage divided by 1.732), shall have the designation “Grd-Y” (grounded-wye) added to the rated maximum voltage. The application of Grd-Y rated PMFSG should be limited to those three-phase applications where the recovery voltage, during switching or fault clearing across any Grd...

SUBSTATION SHIELDING AND GROUNDING PRACTICES BASIC INFORMATION

The following are recommendation based on IEEE STD 525-1992 Shielding practices a) The cable for computer or high-speed data logging applications, using low-level analog signals, should be made up of twisted and shielded pairs. For noncomputer type applications, such as annunciators, shielding may not be required. b) Twisting and shielding requirements for both digital input and digital output signals vary among different manufacturers of computerized instrumentation systems. Separation of digital input cables and digital output cables from each other and from power cables may be required. Where digital inputs originate in proximity to each other, twisted pair multiple conductor cables with overall shield should be used or multiple conductor cable with common return may be permitted, and overall shielding may not be required. Digital output cables of similar constructions may also be permitted. Individual twisted and shielded pairs should be considered for pulse-type circuits. ...

TYPES OF SHUNT REACTOR BASIC INFORMATION

The two general types of construction used for shunt reactors are dry-type and oil-immersed. The construction features of each type, along with variations in design, are discussed under the headings which follow. Dry Type Dry-type shunt reactors generally are limited to voltages through 34.5 kV and are usually applied on the tertiary of a transformer which is connected to the transmission line being compensated. The reactors are of the air-core (coreless) type, open to the atmosphere, suitable for indoor or outdoor application. Natural convection of ambient air is generally used for cooling the unit by arranging the windings so as to permit free circulation of air between layers and turns. The layers and turns are supported mechanically by bracing members or supports made from materials such as ceramics, glass polyester, and concrete. The reactors are constructed as single-phase units and are mounted on base insulators or insulating pedestals which provide the insulation to...

AUTO RECLOSING OF TURBINE-GENERATOR CONSIDERATIONS

Manual closing or autoreclosing without synchronization supervision at line terminals that are in close electrical proximity to turbine-generators can subject them to excessive shaft torques and winding stresses with resultant loss of life of the turbine-generator system. These effects should be studied and evaluated before autoreclosing is initiated by tripping. It is preferable to re-energize a line at a terminal remote from the generator bus, check synchronism between the generator bus and line, and then close the breaker at the generator end. In past years, considerable research and analysis focused on the stresses in the shafts and components of turbine-generators due to switching operations. There is little documentation of actual damage to, or failure of, turbine-generators resulting from autoreclosing or switching. The effects of these stresses induced are cumulative and can be caused by normal switching operations or system faults. Therefore, autoreclosing can be...

TRANSMISSION SYSTEM GROUNDING TEMPORARY OVERVOLTAGE (TOV) AND ARRESTER RATING

The ultimate surge voltage protection is obtained through arrester voltage ratings as low as system grounding conditions will permit during normal and abnormal system conditions. Initially, however, when the surge arrester was adopted as the basic protection device, the equipment design (coordination of major insulating structures) assumed that an “ungrounded neutral” or “100% rated” arrester would be used, unless otherwise specified. In time, after successful service experience with 100% rated arresters (100% of maximum line-line voltage), it was reasoned that lower rated arresters would be suitable on grounded neutral systems. On these systems, the TOV on the unfaulted phases during a line-to-ground fault would bear the same relationship to arrester rating as “maximum line-line voltage” in an ungrounded system. An “effectively grounded” system was then defined in terms of the symmetrical-component sequence resistances and reactances, for which the TOV on an unfaulted pha...

EXTERNAL FUSE SELECTION AND OPERATION OF SHUNT CAPACITOR BANKS

IEEE Std C37.48-1997 covers in detail the application guidelines for high-voltage external capacitor fuses. The energy stored in the healthy capacitors of one series group of parallel-connected capacitors will discharge into the failed capacitor unit of that group and its fuse. The fuse shall be able to interrupt the energy supplied by the parallel group of capacitor units when they are charged to their peak voltage. If the capacitor bank design has an available discharge energy higher than the capacitor units or expulsion fuses can withstand, current-limiting fuses with adequate energy rating should be considered. When ungrounded wye capacitor banks are supplied in an enclosure, current-limiting fuses shall be used to eliminate the arc products that occur with the use of an expulsion fuse. These arc products in the confined enclosure could cause further evolution of the fault. Current-limiting fuses may also be required on enclosed single-group ungrounded wye banks t...

NEUTRAL GROUNDING OF CAPACITOR BANKS – AN INTRODUCTION

The application of large shunt capacitor banks with switched parallel banks in high-voltage transmission systems involves a number of considerations, one of which is grounding. It is generally recommended that the neutral of capacitor banks be grounded only to systems that are effectively grounded. In the event of a phase-to-ground fault, a grounded capacitor bank neutral in an otherwise ungrounded system may lead to high transient overvoltages in the system and capacitor bank as a result of restriking of the arcing fault to ground. One of the main advantages associated with neutral grounding concerns the severity of the recovery voltage across the first pole of the switch to clear, interrupting the charging current of the capacitor bank. The recovery voltage across the first pole to open consists of trapped charges on the capacitors and the variation in the 60 Hz voltage of the system. Due to system parameters and capacitor bank size, the recovery voltage can be app...
free counters