SURGE ARRESTER SPECIFICATIONS SAMPLE 72.5 kV


Surge Arresters w Corona Rings
Below is a sample of a specification of Surge Arrester. Some of the basic parameter are covered. You may use it as a guide in selection and specifying Surge Arresters for your specific needs. Take note that not everything is covered on the specs. Use it only as a guide.

SURGE  ARRESTERS
                  
Brand:   Brand of Choice
Class :   Station Class
Installation:   Outdoor Type
Voltage Rating (kV rms) : 60
MCOV Rating (kV rms) : 48
Front-of-Wave Protective Level (kV crest):  175
Maximum Discharge Voltage (kV crest) : - 1.5 KA  125
Switching Surge Protective Level (kV crest)  @ 500 A :  117
Creepage Distance :  68 in.
Insulation Withstand Voltage :
    - 1.2/50 Impulse (kV Crest) 358
    - 60Hz dry 60 sec (kV rms) 200
Rated Arrester Discharge Energy   >9 kJ/KV of MCOV
Conductive Material :  Metal Oxide
Housing : Silicon Rubber/Polymer
Line Teminal Connection: NEMA Four-hole Pad
Ground Terminal Connection:  NEMA Four-hole Pad
Mounting Arrangement :  Mounting Base Located on Bottom (Standard Mounting)

Comments

Popular posts from this blog

TRANSMISSION LINE CONDUCTOR ICE LOADING BASICS AND TUTORIALS

LONGEST POWER TRANSMISSION LINE IN THE WORLD

INSULATION COORDINATION IEC STANDARD APPROACH BASICS AND TUTORIALS

free counters