Posts

Showing posts from May, 2013

TYPES OF SHUNT REACTOR BASIC INFORMATION

The two general types of construction used for shunt reactors are dry-type and oil-immersed. The construction features of each type, along with variations in design, are discussed under the headings which follow. Dry Type Dry-type shunt reactors generally are limited to voltages through 34.5 kV and are usually applied on the tertiary of a transformer which is connected to the transmission line being compensated. The reactors are of the air-core (coreless) type, open to the atmosphere, suitable for indoor or outdoor application. Natural convection of ambient air is generally used for cooling the unit by arranging the windings so as to permit free circulation of air between layers and turns. The layers and turns are supported mechanically by bracing members or supports made from materials such as ceramics, glass polyester, and concrete. The reactors are constructed as single-phase units and are mounted on base insulators or insulating pedestals which provide the insulation to...

AUTO RECLOSING OF TURBINE-GENERATOR CONSIDERATIONS

Manual closing or autoreclosing without synchronization supervision at line terminals that are in close electrical proximity to turbine-generators can subject them to excessive shaft torques and winding stresses with resultant loss of life of the turbine-generator system. These effects should be studied and evaluated before autoreclosing is initiated by tripping. It is preferable to re-energize a line at a terminal remote from the generator bus, check synchronism between the generator bus and line, and then close the breaker at the generator end. In past years, considerable research and analysis focused on the stresses in the shafts and components of turbine-generators due to switching operations. There is little documentation of actual damage to, or failure of, turbine-generators resulting from autoreclosing or switching. The effects of these stresses induced are cumulative and can be caused by normal switching operations or system faults. Therefore, autoreclosing can be...

TRANSMISSION SYSTEM GROUNDING TEMPORARY OVERVOLTAGE (TOV) AND ARRESTER RATING

The ultimate surge voltage protection is obtained through arrester voltage ratings as low as system grounding conditions will permit during normal and abnormal system conditions. Initially, however, when the surge arrester was adopted as the basic protection device, the equipment design (coordination of major insulating structures) assumed that an “ungrounded neutral” or “100% rated” arrester would be used, unless otherwise specified. In time, after successful service experience with 100% rated arresters (100% of maximum line-line voltage), it was reasoned that lower rated arresters would be suitable on grounded neutral systems. On these systems, the TOV on the unfaulted phases during a line-to-ground fault would bear the same relationship to arrester rating as “maximum line-line voltage” in an ungrounded system. An “effectively grounded” system was then defined in terms of the symmetrical-component sequence resistances and reactances, for which the TOV on an unfaulted pha...

EXTERNAL FUSE SELECTION AND OPERATION OF SHUNT CAPACITOR BANKS

IEEE Std C37.48-1997 covers in detail the application guidelines for high-voltage external capacitor fuses. The energy stored in the healthy capacitors of one series group of parallel-connected capacitors will discharge into the failed capacitor unit of that group and its fuse. The fuse shall be able to interrupt the energy supplied by the parallel group of capacitor units when they are charged to their peak voltage. If the capacitor bank design has an available discharge energy higher than the capacitor units or expulsion fuses can withstand, current-limiting fuses with adequate energy rating should be considered. When ungrounded wye capacitor banks are supplied in an enclosure, current-limiting fuses shall be used to eliminate the arc products that occur with the use of an expulsion fuse. These arc products in the confined enclosure could cause further evolution of the fault. Current-limiting fuses may also be required on enclosed single-group ungrounded wye banks t...

NEUTRAL GROUNDING OF CAPACITOR BANKS – AN INTRODUCTION

The application of large shunt capacitor banks with switched parallel banks in high-voltage transmission systems involves a number of considerations, one of which is grounding. It is generally recommended that the neutral of capacitor banks be grounded only to systems that are effectively grounded. In the event of a phase-to-ground fault, a grounded capacitor bank neutral in an otherwise ungrounded system may lead to high transient overvoltages in the system and capacitor bank as a result of restriking of the arcing fault to ground. One of the main advantages associated with neutral grounding concerns the severity of the recovery voltage across the first pole of the switch to clear, interrupting the charging current of the capacitor bank. The recovery voltage across the first pole to open consists of trapped charges on the capacitors and the variation in the 60 Hz voltage of the system. Due to system parameters and capacitor bank size, the recovery voltage can be app...
free counters